SECTION 09200
|
| |
Rapid Set® EISENWALL®
PREMIUM STUCCO SYSTEM
(CONVENTIONAL APPLICATION)
|
| |
NOTE TO SPECIFIER
THE FOLLOWING SPECIFICATION HAS BEEN PREPARED TO ASSIST
ARCHITECTS AND DESIGN PROFESSIONALS IN THE PREPARATION
OF PROJECT MASTER SPECIFICATIONS. THIS SPECIFICATION
IS BASED UPON THE MASTERFORMAT (1995) DEVELOPED BY THE
CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI), AND CAN
BE INCORPORATED INTO MOST MASTER SPECIFICATIONS WITH
MINIMAL EDITING.
EDIT AND MODIFY AS NECESARY TO SUIT THE PROJECT MASTER
SPECIFICATION. DELETE ANY ITEMS THAT ARE NOT APPLICABLE
AND VERIFY THAT REFERENCED SECTION NUMBERS AND TITLES
ARE CORRECT. CONTACT Rapid Set®Ò PRODUCTS FOR
ANY ADDITIONAL INFORMATION OR SPECIFICATIONS ASSISTANCE,
WRITING, AND ADAPTATION.
|
| |
|
PART I - GENERAL
PART II - PRODUCTS
PART III - EXECUTION
|
| |
____________________________________
PART I - GENERAL
SUMMARY:
Provide all labor, materials,
equipment and accessories necessary for compliance
with this section and installation of Rapid Set® EISENWALL®
Premium Stucco System.
RELATED SECTIONS: |
| |
- 03300 - Cast-in-Place Concrete
- 04200 - Unit Masonry
- 05400 - Light gauge cold-formed steel framing
- 06100 - Rough Carpentry: Wood framed construction
- 06160 - Sheathing
|
| |
REFERENCE STANDARDS: |
| |
- UBC - Uniform Building Code
- ICBO-ER 5102
- ASTM C1063 - Installation of Lathing and Furring
for portland cement Based Plaster
- ASTM C847 - Standard Specification for Metal Lath
- Plaster and Drywall Systems Manual, Third Edition
|
| |
DESCRIPTION:
The Rapid Set® EISENWALL® Premium Stucco System consists of Rapid Set® EISENWALL® Cement
mixed with a high quality graded plaster sand, reinforced
with metal lath. The system is installed on exterior
walls of wood, steel, masonry, or concrete construction.
|
| |
SUBMITTALS:
Reference Section 01300 - Submittal Procedures, submit the following items:
|
| |
- All product data sheets, specifications,
and details that pertain to the project, for architect
approval.
- Manufacturer's certificate of Approved Applicator
status, or letter from manufacturer stating temporary
approval pending jobsite training and certification.
- Manufacturer's Application Guidelines.
- Samples: Samples of an adequate size and number
as specified by the architect to show color and texture
of finish coat. Final applied colors and textures
shall match Architect's approved samples. Samples
shall be retained on site throughout the construction
process.
|
| |
QUALITY ASSURANCE:
- System components shall be manufactured or approved for use by CTS Cement
Manufacturing Corporation/Rapid Set® Products, and
shall be distributed by the same or one of its authorized
dealers.
- Mock-Up: Upon request, provide a complete system sample panel of specified size using
workmen, equipment, and techniques proposed for use
on the project. Sample shall be reviewed for uniformity
of depth and thickness, finish color and texture,
and overall quality of construction. The panel shall
remain on-site throughout the construction process.
The approved panel shall become the standard of comparison
for finished work for the project. Upon project completion,
dispose of the sample panel appropriately.
- Applicator/Contractor shall be experienced with the application of the EISENWALL®
Premium Stucco System, and possess an Approved Applicator
Certificate stating such. Alternatively, the applicator
shall obtain a letter from the Manufacturer stating
temporary approval and shall have a manufacturers'
representative on-site for initial application.
|
| |
DELIVERY, STORAGE, AND HANDLING:
- Reference Section 01660 - Product Storage and Handling Requirements.
- Materials shall be delivered in the manufacturers'
original intact packaging labeled plainly with the
manufacturers' name and brand, address and evaluation
report number, identification of components, and weight
of packaged mix.
- Keep materials dry until used. Keep materials off
the ground, under cover, and clear of damp walls or
other damp surfaces. Store bulk sand in a well drained
area on a clean, solid surface. Cover sand to prevent
contamination with foreign matter.
|
| |
PROJECT CONDITIONS:
- Environmental Requirements:
Maintain ambient and surface temperature between 40
and 100 degrees Fahrenheit during material application
and curing periods.
- Installation of the EISENWALL®
Premium Stucco System shall be coordinated with all
other trades and conditions so as to not impede overall
general construction.
- Sufficient manpower shall be provided
to insure continuous application, timely finishing,
and a product free of cold joints, scaffolding lines,
variations in texture, etc.
- Protect adjacent surfaces not
specified to receive finishing, with drop cloths,
waterproof paper, or other means to maintain them
free of material splashes, overspray, water, or debris.
|
| |
PART II - PRODUCTS MANUFACTURERS:
- Acceptable basecoat
material will be manufactured by the following:
CTS Cement Manufacturing Corporation/Rapid Set® Products
11065 Knott Avenue, Suite A
Cypress, California 90630
Ph: 800-929-3030 Fax: 714-379-8270
- All lath, trims, accessories, and finishes shall be manufactured by specified manufacturer,
or manufacturer approved by above [Rapid Set® Products].
- Technical / Specifications Consultant:
Ken Vallens
Product Development Engineer:
Rapid Set® Products
Ph: 800-929-3030 x129
|
| |
MATERIALS AND COMPONENTS:
Basecoat Components:
|
| |
- A. Cement shall be Rapid Set® EISENWALL® Cement; a rapid-setting,
high early-strength, low shrinkage plastic cement, in
88lb. bags. Cement shall meet performance specifications below:
|
| |
- Minimum Compressive Strength (ASTM C-109)
6 hr 400 psi
24 hr 1500 psi
3 day 2900 psi
28 day 3500 psi
- Set Time (ASTM C-403)
Initial (minimum) 90 min.
Final (maximum) 150 min.
- Shrinkage (ASTM C-596 mod.)
28 day maximum drying shrinkage -.019%
|
| |
-
Sand must be clean and free from deleterious amounts
of loam, clay, silt, soluble salts and organic matter.
Sampling and testing must comply with ASTM C-144. Sand
must be graded within the following limits:
|
| |
- Percent
by weight retained on:
US standard sieve Minimum (+2%) Maximum (+2%)
|
| |
|
No. 4
No. 8
No. 16
No. 30
No. 70
No. 95 |
----- 0
0 to 10
10 to 40
30 to 65
70 to 90
95 to 100 |
| |
-
Water must be clean and free from deleterious amounts
of silt and dissolved salts.
|
| |
-
Lathing Materials: Per specification. For vertical surfaces.
|
| |
- Expanded self-furred metal lath
fabricated from copper bearing steel, with weight
of 3.4 pounds per square yard, and galvanized.
|
| |
- Accessories: all corner reinforcement / aid,
casing beads, foundation weep screed, and control/expansion
joints shall be galvanized steel and per drawings/specifications.
- Fasteners: Comply with ASTM C-1063,
or UBC, whichever is more stringent, for type and
size of fastener required to rigidly secure materials
in place.
PART III - EXECUTION PREPARATION:
- All work shall be performed
by skilled craftsmen, experienced in this type of
work.
- Examine substrate to insure that
finished surfaces will be true, level, and plumb without
requiring additional or uneven thickness of coatings.
Verify that concrete and masonry are free of dust,
loose particles, oil and other foreign matter which
would adversely affect the bond of base coat. Notify
the proper authority, in writing, of any discrepancies
found in the substrate. Beginning of installation
indicates acceptance of existing conditions.
- Concrete/Masonry: Apply a bonding/sealing
agent to concrete and masonry before application of
base coat. Apply the bonding agent in accordance with
manufacturers instructions.
INSTALLATION:
Install Rapid Set® EISENWALL®
Premium Stucco System per manufacturers guidelines
for application. Installation shall comply with UBC
except as modified in ICBO ER-5102.
- Weather Resistant Barrier: Install
two layers of type D building paper complying with
UBC 14-1. Building paper shall be applied horizontally,
with the upper layer lapped over the lower layer a
minimum of four inches. At vertical joints, a minimum
lap of six inches is required. Stagger joint spacing
of both layers of building paper. Application of the
barrier must comply with section 1402.1 of the code.
- Metal lath and accessories: Install per UBC and ASTM C-1063, whichever is more stringent.
|
| |
- Install trims prior to application of metal lath.
- Metal lath shall be discontinuous under all control joints and expansion joints, providing
free-floating panels.
- Install corner reinforcement/aid at all exterior corners.
|
| |
- Mix and proportion Rapid Set® EISENWALL® Cement per manufacturers application guidelines.
- Apply basecoat by hand trowelling or gun application, in one coat, to 3/4" thickness,
using sufficient pressure and mechanical force, to embed metal lath, fill all spaces behind metal lath,
and provide a mechanical key with metal lath.
*** Alternatively, basecoat can be
applied in two coats, 3/8" thickness each, with
the second coat being applied as soon as the first
coat has attained sufficient rigidity to accept the
mechanical force of application without damage.
- Over concrete and masonry, apply
basecoat in one coat to 1/2" thickness. Base
coat shall be brought out to grounds, straightened
to a true surface, and finished with sufficient texture
to assure adequate bond with finish coat.
- Moist cure basecoat for minimum
2 hours by providing light fog of clean, potable water
as needed to maintain wet sheen.
- Apply specified finish coat to
1/8" thickness, per manufacturers guidelines/instructions,
as soon as basecoat is sufficiently hydrated. Basecoat
may require light misting to ensure even suction.
Apply finish coat evenly and consistently in order
to achieve uniformity in color and texture.
- Tolerances: Maximum variation
from true flatness: 1/8" in 10ft.
- Complete all work in the same
plane and panel each day, Do NOT stop short, such
as at expansion joints, etc.
ACCEPTANCE:
- Upon completion, clean up overspray/spatters,
remove all tools, equipment and unused materials.
Remove all trash and protective masking, and clean
all material from joints. Leave the work area in a
clean, orderly state.
View Eisenwall Technical Bulletin |
| |
|